Power Modules
4.2 Blocksize Power Modules (PM240-2)
AC Drive
110 Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
Line voltage 1-phase/3-phase 200 … 240 VAC ± 10%
3-phase 200 … 240 VAC
±10%
Order number
without integrated line filter
with integrated line filter
6SL3210–
1PB21-4UL0
1PB21-4AL0
6SL3210–
1PB21-8UL0
1PB21-8AL0
6SL3211–
1PB21-8UL0
1PB21-8AL0
6SL3210–
1PC22-2UL0
1PC22-2AL0
6SL3210–
1PC22-8UL0
1PC22-8AL0
3)
Without line filter
kg
5,0
5,0
5,8
5,0
5,0
Rated output of a typical standard induction motor at 230 V.
The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating
(based on I
rated
) for a line impedance corresponding to u
k
= 1%.
Max. motor cable length 50 m (shielded) for PM240-2 Power Modules with integrated line filter to maintain the limit
values of EN 61800-3 Category C2.
4)
Power loss in the cabinet: 0,075 kW. The remaining power loss is dissipated via the heat sink.