EasyManuals Logo

Siemens SIMATIC PCS 7 SMART User Manual

Siemens SIMATIC PCS 7 SMART
210 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #143 background imageLoading...
Page #143 background image
Compiling the OS
You must execute the "Compiles OS" function after you finish configuring all of the data in
SIMATIC Manager and before you start configuring the OS data of the OS. All the data from
SIMATIC Manager such as variables, messages, texts, hardware and connection
configurations must be known to the OS.
Starting the OS
You have to start the OS to continue configuring it. Then, perform other steps in the WinCC
Explorer.
9.4.2 Procedure
9.4.2.1 Editing picture properties
Introduction
To edit the picture properties:
Change the name of the picture.
Select the option for creating block icons.
Prerequisites
The color_gs project is open in SIMATIC Manager.
The plant view is activated.
Procedure for Changing the Picture Name
1. Select the "color_gs_prj_MP\color_gs_prj_Prj\Plant1\ RMT1" folder in the tree view.
2. Select "Picture(3)" in the detail view.
3. Select Edit > Object Properties.
The "Properties - WinCC Picture: Picture(3)" dialog box opens with the "General" tab active.
Configuring the operator station
9.4 Working in the SIMATIC Manager
PCS 7 SMART Getting Started - Part 1 (V9.0 with APL)
Getting Started, 12/2017, A5E42181435-AA 143

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC PCS 7 SMART and is the answer not in the manual?

Siemens SIMATIC PCS 7 SMART Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC PCS 7 SMART
CategoryControl Systems
LanguageEnglish

Related product manuals