EasyManua.ls Logo

Siemens SIMATIC PCS 7 SMART - Process-Related Meaning of the CFC_FC111 CFC Chart; Process-Related Meaning of the CFC_LI111 CFC Chart; Process-Related Meaning of the CFC_NP111 CFC Chart

Siemens SIMATIC PCS 7 SMART
210 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.3.3 Process-Related meaning of the "CFC_FC111" CFC chart
CFC_FC111
CFC_FC111 is used to control the dosing quantity and dosing speed. In this case, the blocks
mean the following:
The "Pcs7AnIn" block provides the currently dosed volume at the "PV_Out" output and
transfers this measured value to the "PV (process value) input of the "DoseL" block.
The "PIDConL" block delivers the manipulated variable of the flow.
"DoseL" delivers the setpoint for the flow (manipulated value for the "PIDConL" block) and
checks the dosing quantity.
The manipulated variable for the valve is sent to the "MV" output of the "PIDConL" block.
Then, it is fed to the "MV_Trk" input of the "PIDConL" block in the absence of manipulated
variable feedback from the process.
The "Pcs7AnOu" block sends out the manipulated variable to the valve.
6.3.4 Process-Related meaning of the "CFC_LI111" CFC chart
CFC_LI111
CFC_LI111 is used for controlling and simulating the fill level. In this case, the blocks mean
the following:
The Pcs7AnIn" block reads the fill level of the raw material tank and outputs the current
value at "PV_Out" output.
The "PV_Out" output is interconnected with the "OutTrk" input of the "Integral" block.
The "Out" output is interconnected with the "PV" input of the "MonAnL" block.
The "Mul04" block is used to simulate the quantity which is taken from the reservoir at the
given point of time.
6.3.5 Process-Related meaning of the "CFC_NP111" CFC chart
CFC_NP111
CFC_NP111 is used for pump controlling. In this case, the blocks mean the following:
The "Pcs7DiIn" block supplies the current state of the pump - on or off, at the "PV_Out"
output.
This value is interconnected to the "MotL" input (feedback ON) of the "FbkRun" block where
it is evaluated.
Creating CFCs
6.3 Technological significance of the charts in the project
PCS 7 SMART Getting Started - Part 1 (V9.0 with APL)
72 Getting Started, 12/2017, A5E42181435-AA

Table of Contents

Related product manuals