Instructions for Design of Drives in Conformance with EMC Regulations 05.2003
6SE7087-6QX70 (Version AD) Siemens AG
3-26 Compendium Motion Control SIMOVERT MASTERDRIVES
3.6 Assignment of SIMOVERT MASTERDRIVES, radio
interference suppression filters and line reactors
The assignment of SIMOVERT MASTERDRIVES, radio interference
suppression filters and line reactors is specified in Catalog DA65.11
and the Operating Instructions for the 6SE70 radio interference
suppression filters.
The 6SE70 radio interference suppression filters were checked to make
sure they maintain the limit values, using layouts consisting of
SIMOVERT MASTERDRIVES and the associated line reactors. The
components were mounted in cabinets (Type 8MC) in observance of
the specified rules. The motor feeder cable was 30 m long.
3.7 Specified standards
EN 55011: 1991 Limits and methods of measurement of radio
disturbance characteristics of industrial, scientific
and medical (ISM) radio-frequency equipment
EN 50081-1: 1992 Generic emission standard
Part 1: Residential, commercial and light industry
EN 50081-2: 1993 Generic emission standard
Part 2: Industrial environment
EN 50082-1: 1992 Generic immunity standard
Part 1: Residential, commercial and light industry
EN 50082-2: 1995 Generic immunity standard
Part 2: Industrial environment
EN 61800-3: 1996 EMC product standard including special test
methods for variable-speed electric drive units