Configuration and Connection Examples 12.2010
6SE7087-6QX70 (Version AM) Siemens AG
2-20 Compendium Motion Control SIMOVERT MASTERDRIVES
2.4.3 General information about MASTERDRIVES
MASTERDRIVES units are available with two different modes of
control:
MC Motion Control
VC Vector Control
The control variant does not influence the internal and external safety
circuitry.
Pulse disconnection by the safety relay which is needed to implement
the STO function is always performed on the power module. This is the
case irrespective of the control variant.
There are various methods of achieving safe pulse suppression
depending on the type of construction.
Type of construction Unit rating Safety circuit design
Compact PLUS Small 0.55 kW to 4 kW As a separate module on the power section
(option K80)
Compact PLUS Large 5.5 kW to 18.5 kW On the power section (option K80)
Compact PLUS Large LE 22 kW to 37 kW As a separate module on the power section
(option K80)
Compact converter 18.5 kW to 37 kW On power section module PEU
Compact inverter 2.2 kW to 37 kW On power section module PEU
Chassis 1 45 kW to 200 kW Implemented by SSB module (option K80),
piggyback on PSU1 power supply
Chassis 2 250 kW to 1.2 kW
SSB module (option K80) as for Chassis 1, but
directly integrated in the unit