Instructions for Design of Drives in Conformance with EMC Regulations 05.2003
6SE7087-6QX70 (Version AD) Siemens AG
3-8 Compendium Motion Control SIMOVERT MASTERDRIVES
In the case of analog signal cables, low-frequency noise can arise if
the shield is connected at both ends (hum is coupled-in). In this case,
the shield must only be connected at one end at the SIMOVERT
MASTERDRIVES. The other end of the shield should be grounded
through a capacitor (e.g. 10 nF/100 V type MKT). This capacitor
enables the shield to be connected at both ends after all as far as high-
frequency noise is concerned.
3.4 EMC planning
If two units are not electromagnetically compatible, the noise radiated
by the noise transmitter can be reduced, or the noise immunity of the
noise receiver can be increased. Noise sources are often power
electronic units with a large current drain. Complex filters are necessary
to reduce their noise emission. Noise receivers especially include
control devices and sensors/transmitters, as well as their evaluation
circuit. Not so much effort and cost is required to increase the noise
immunity of low-power units. In industrial environments, it is therefore
more cost-effective to increase the noise immunity than to reduce the
noise emission.
To maintain the "Second environment" limit value class specified in EN
55011, the radio interference voltage at the mains connection point can
be a maximum of 79 dB (µV) between 150 kHz and 500 kHz, and a
maximum of 73 dB (µV) between 500 kHz und 30 MHz. When
expressed in volts, these values are 9 mV and 4.5 mV respectively!
Before radio interference measures can be applied, it must first be
clarified at which locations you or your customer require EMC. See the
following example:

Table of Contents

Other manuals for Siemens simovert masterdrives

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens simovert masterdrives and is the answer not in the manual?

Siemens simovert masterdrives Specifications

General IconGeneral
BrandSiemens
Modelsimovert masterdrives
CategoryDC Drives
LanguageEnglish

Related product manuals