11.9.5 Selection of the braking resistor
The braking resistor is connected to the chopper of the rectifier unit.
During rating, it is assumed that the drives of the x and z axes can
brake simultaneously.
♦ The maximum braking power levels of the two inverters are
therefore added together.
P P kW kW kW
br br Invmax
.. .==−−=−
408 332 74
♦ For the mean braking power, the individual mean values are also
added together.
P P kW kW kW
br mean br Inv mean
==−−=−
0146 0 28 0 426.. .
♦ A 6SE7018-0ES87-2DC0 braking resistor of 80 Ω with P
20
= 5 kW
is necessary.
PkW
br max
.= 74 < 15 7 5
20
..⋅=PkW
PkW
br meen
= 0 426.
< PkW
20
45 111/. .=