Parameter
Description Data Read/write
P123*
Stator React
123
Function parameter for entering the stator reactance of a
connected induction motor. The value to be entered
corresponds to the stator reactance of a winding phase at
40% of the rated motor current. The parameter value is
calculated during the automatic calculation of derived
motor data (P115).
Init: 0,00
Min: 0,00
Max: 655,00
Unit: Ohm
Indices: -
Type: O2
Menus:
- Parameter menu
+ Motor/encoder
+ Motor data
- Drive setting
- Upread/free access
Changeable in:
- Drive setting
P124*
Rotor TimeConst
124
Function parameter for entering the rotor time constant of
a connected induction motor. The parameter value is
calculated during the automatic calculation of derived
motor data (P115).
Init: 0
Min: 0
Max: 10000
Unit: ms
Indices: -
Type: O2
Menus:
- Parameter menu
+ Motor/encoder
+ Motor data
- Drive setting
- Upread/free access
Changeable in:
- Drive setting
P127
R(Rot)Corr'nTmp
127
Parameter is not used. Init: 70,0
Min: 12,5
Max: 400,0
Unit: %
Indices: -
Type: O2
Menus:
- Parameter menu
+ Control/gating unit
+ Current control
- Upread/free access
Changeable in:
- Ready to switch on
P128*
Max Current
128
Function parameter for entering the maximum current
(r.m.s. value of the fundamental component). The output
current is limited to the value entered. The limitation of the
output current serves to protect the connected motor.
The maximum current that can be input is limited by
converter current parameter P072. Any derating that may
be necessary because of increased pulse frequency is not
taken into account until r129.
In function diagram 370.5
Init: 6,3
Min: 0,0
Max: 2000,0
Unit: A
Indices: -
Type: O2
Menus:
- Parameter menu
+ Motor/encoder
+ Motor data
- Drive setting
- Upread/free access
Changeable in:
- Drive setting
- Ready to switch on
r129
I(max,set)
129
Visualization parameter for displaying the actually
effective maximum current (r.m.s. value of the
fundamental component). If utilization of the converter or
inverter exceeds 100 % (i2t calculation) or if the maximum-
current limit has been reduced, the displayed value
deviates from the value set in P128. The maximum
current can be reduced, for example, by operation at a
pulse frequency (P340, P357) > 3kHz.
In function diagram 370.5
Dec.Plc.: 1
Unit: A
Indices: -
Type: I2
Menus:
- Parameter menu
+ Motor/encoder
+ Motor data
- Upread/free access
16
Siemens AG 6SE7087-6QX70 (Edition AL)
SIMOVERT MASTERDRIVES Compendium Motion Control