Parameter
Description Data Read/write
P174*
S.PosCorr'nV
174
BICO parameter for selecting the connector from which
the corrected position value is to be read in.
In function diagram 330.5
Init: 0
Unit: -
Indices: -
Type: L2 ,K
,K
Menus:
- Parameter menu
+ Control/gating unit
+ Position control
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P175*
S.Pos Corr'n
175
BICO parameter for selecting the binectors from which the
commands for correcting the actual position are to be
read in.
Index 1: Addition of the corrected value
Index 2: Subtraction of the corrected value
index1: 303
Unit: -
Indices: 2
Type: L2 ,B
Menus:
- Parameter menu
+ Control/gating unit
+ Position control
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P176*
S.Ref SetV
176
BICO parameter for selecting the connector from which
the actual position is to be read in during the Reference-
Point Detection operating mode.
Init: 0
Unit: -
Indices: -
Type: L2 ,K
,K
Menus:
- Parameter menu
+ Control/gating unit
+ Position control
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P177*
S.Release Ref
177
BICO parameter for selecting the binector from which the
command for releasing the Reference-Point Detection
operating mode is to be read in.
Init: 307
Unit: -
Indices: -
Type: L2 ,B
Menus:
- Parameter menu
+ Control/gating unit
+ Position control
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P178*
S.Rough Pulse
178
BICO parameter for selecting the binector from which the
rough pulse is to be read in during the Reference-Point
Detection operating mode.
Init: 0
Unit: -
Indices: -
Type: L2 ,B
Menus:
- Parameter menu
+ Control/gating unit
+ Position control
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P179*
S.RelMValVolts
179
BICO parameter for selecting the binector from which the
command for releasing the measured-value memory is to
be read in.
Init: 308
Unit: -
Indices: -
Type: L2 ,B
Menus:
- Parameter menu
+ Control/gating unit
+ Position control
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
31