Parameter
Description Data Read/write
P240*
n-Reg Time
240
Function parameter for entering the reset time of the
speed controller.
index1: 50
Min: 0
Max: 4095
Unit: ms
Indices: 4
,FDS
Type: O2
Menus:
- Parameter menu
+ Control/gating unit
+ Speed control
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P241*
S.SetV n-Reg1
241
BICO parameter for selecting the connector from which
the set value for the I component of the speed controller is
to be read in.
index1: 0
Unit: -
Indices: 2
,BDS
Type: L2 ,K
Menus:
- Parameter menu
+ Control/gating unit
+ Speed control
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P242*
S.Set n-Reg1
242
BICO parameter for selecting the binector from which the
command for setting the I component of the speed
controller is to be read in. The set value is adopted when
the edge of the signal rises.
index1: 0
Unit: -
Indices: 2
,BDS
Type: L2 ,B
Menus:
- Parameter menu
+ Control/gating unit
+ Speed control
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P243*
S.n-Reg1 STOP
243
BICO parameter for selecting the binector from which the
command for halting the I component of the speed
controller is to be read in. When the value of the signal
connected to the binector is a logical "1", the I component
of the speed controller is halted. From then onwards, the
speed controller only works as a P controller.
index1: 0
Unit: -
Indices: 2
,BDS
Type: L2 ,B
Menus:
- Parameter menu
+ Control/gating unit
+ Speed control
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P244*
S.Speed ext.
244
Souce for speed measurement of the external encoder.
Connector KK90 or KK104 can be used here.
Init: 0
Unit: -
Indices: -
Type: L2 ,K
,K
Menus:
- Parameter menu
- Upread/free access
Changeable in:
- Ready to switch on
P245*
S.Droop
245
BICO parameter for selecting the connector from which
the input signal for the droop is to be read in. Preferably,
the I component of the speed controller (K0155) is
connected here.
index1: 0
Unit: -
Indices: 2
,BDS
Type: L2 ,K
Menus:
- Parameter menu
+ Control/gating unit
+ Speed control
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P246*
Scale Droop
246
Function parameter for scaling the droop. Parameter
values greater than 0 lead to lowering of the speed
setpoint when load is applied to the drive and thus to a
deviation of the speed from the main setpoint.
index1: 0,0
Min: 0,0
Max: 100,0
Unit: %
Indices: 4
,FDS
Type: O2
Menus:
- Parameter menu
+ Control/gating unit
+ Speed control
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P247
Scale kp n-Limtr
247
Function parameter for increasing the gain (Kp) of the
speed limiting controller. The increase is the result of
multiplying with this factor.
In function diagram 370.3
index1: 1,0
Min: 0,1
Max: 100,0
Unit: -
Indices: 4
,FDS
Type: O2
Menus:
- Parameter menu
+ Control/gating unit
+ Speed control
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
41
Siemens AG 6SE7087-6QX70 (Edition AL)
SIMOVERT MASTERDRIVES Compendium Motion Control