Parameter
Description Data Read/write
P370*
Quick Param
370
Function parameter for starting quick parameterization.
When quick parameterization is selected, the unit is
parameterized according to the selected parameter
modules.
0 = No quick parameterization
1 = Start quick parameterization
After quick parameterization has been completed, the
parameter is reset to 0.
Init: 0
Min: 0
Max: 1
Unit: -
Indices: -
Type: O2
Menus:
- Parameter menu
+ Functions
- Quick parameterization
- Upread/free access
Changeable in:
- Ready to switch on
P372*
Simulation Mode
372
Function parameter for selecting simulated operation.
Simulated operation allows test operation of the drive
without DC link voltage. The unit must, therefore, have an
external 24 V supply.
Simulated operation can not be selected if the DC link
voltage is more than 5 % of the rated DC link voltage.
0 = Simulated operation not active
1 = Simulated operation active
Init: 0
Min: 0
Max: 1
Unit: -
Indices: -
Type: O2
Menus:
- Parameter menu
+ Functions
- Upread/free access
Changeable in:
- Ready to switch on
P373*
Src Enable CLC
373
Function parameter for parameterizing the function cyclic
load compensation:
Enables:
Index 1: Binector input: Enable of function
Index 2: Binector input: Enable of learn function
index1: 0
Unit: -
Indices: 2
Type: L2 ,B
Menus:
- Parameter menu
+ Functions
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P374
Src Learn CLC
374
Function parameter for parameterizing the function cyclic
load compensation:
Connector input for the source for compensation by the
function.
Init:
Unit: -
Indices: -
Type: L2 ,K
,K
Menus:
- Parameter menu
+ Functions
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P375*
CLC Periodicity
375
Function parameter for parameterizing the cyclic load
compensation function:
Describes the load period to be compensated. This value
refers to the value of the position in position sensing.
Init: 4096
Min: 10
Max:
2147483647
Unit: -
Indices: -
Type: I4
Menus:
- Parameter menu
+ Functions
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P376
CLC Parameter 1
376
Function parameter for parameterizing the cyclic load
compensation function:
Time constants:
Index 1: Smoothing time constant for smoothing the
output signal (in ms)
Index 3: Latency resulting from dead times and additional
filter-dependent phase displacements (in ms)
index1: 2,0
Min: 0,0
Max: 3000,0
Unit: ms
Indices: 2
Type: O2
Menus:
- Parameter menu
+ Functions
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P377
CLC Parameter 2
377
Function parameter for parameterizing the cyclic load
compensation function:
Index 1:
Learning rate: The percentage of the learing input
determined by this parameter is transferred to the learning
memory in every cycle.
Index 2:
Damping: The percentage of the memory determined by
this parameter is removed from the learning memory in
every cycle.
index1: 40
Min: 0
Max: 100
Unit: %
Indices: 2
Type: O2
Menus:
- Parameter menu
+ Functions
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
58
Siemens AG 6SE7087-6QX70 (Edition AL)
SIMOVERT MASTERDRIVES Compendium Motion Control