Parameterization 03.2010
6SE7087-6QX70 (Version AL) Siemens AG
5-10 Compendium Motion Control SIMOVERT MASTERDRIVES
The following example shows the individual operator control steps to be
carried out on the PMU for a parameter reset to factory setting.
P
P053
∇
∇
Set P053 to 0002 and grant parameter access via PMU
P
0000 0001 0002 P053
∇
P053
Select P060
P060
P
P060
Set P060 to 0002 and select "Fixed settings" menu
1
Select P970
P
P970
Set P970 to 0000 and start parameter reset
1
P
2 P060
∇
P
0 °005
∇
∇
P060 P970
...
Example