EasyManua.ls Logo

Siemens simovert masterdrives

Siemens simovert masterdrives
1547 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
03.2010
Siemens AG 6SE7087-6QX70 (Version AL)
SIMOVERT MASTERDRIVES Compendium Motion Control 9
Number / Fault Cause Counter-measure
F085
Add. CB initialization
fault
A fault has occurred during initialization of the
CB board.
Fault value r949:
1: Board code incorrect
2: TB/CB board not compatible
3: CB board not compatible
5: Error in configuration data
6: Initialization timeout
7: TB/CB board double
10: Channel error
Check the T300 / CB board for correct
contacting and check the CB initialization
parameters:
- P918.02 CB Bus Address,
- P711.02 to P721.02 CB Parameters 1 to 11
F087
SIMOLINK initialization
fault
A fault has occurred during initialization of the
SLB board.
- Replace CU (-A10), or replace the unit
(Compact PLUS type)
- Replace SLB
F099
Friction characteristic
record
Recording of the friction characteristic was
interrupted or not done at all.
Fault value r949 gives the cause (bit coded):
Bit Meaning Value displayed
0 Pos. speed limit 1
1 Neg. speed limit 2
2 Releases missing: 4
direction of rotation, inverter, controller
3 Speed controller connecting 8
4 Interrupt through cancellation of the 16
record command
5 Illegal dataset changover 32
6 Time exceeded 64
7 Measuring error 128
F109
Mld R(L)
The rotor resistance determined during
measurement of the direct current deviates too
greatly.
- Repeat measurement
- Enter data manually
F111
MId DSP
A fault has occurred during the Mot Id.
r949=1 The current does not build up when
voltage pulses are applied
r949=2 (only for P115=4) The difference
between speed setpoint and actual value is
too large during measurement
r949=3 (only for P115=4) The magnetizing
current determined is too high.
r949=4 (only for P115=4) Two phases of the
motor or the a/b tracks of the encoder were
swapped when they were connected.
r949=121 The stator resistance P121 is not
determined correctly
r949=124 The rotor time constant P124 is
parameterized with the value 0 ms
r949=347 The valve voltage drop P347 is not
determined correctly
- Repeat measurement
- When r949=1 Check motor cables
- When r949=2 Avoid mechanical stressing of
the motor during the measurement; if the fault
occurs directly after the start of the motor
identification check the encoder and motor
cables.
- When r949=3: Check the motor rating plate
data stored (ratio Vrated / Irated does not
correspond with the measured inductance)
F112
Mid X(L)
A fault has occurred during measurement of
the motor inductances or leakages.
- Repeat measurement
F114
MId OFF
The converter has automatically stopped the
automatic measurement due to the time limit
up to power-up having been exceeded or due
to an OFF command during the measurement,
and has reset the function selection in P115.
Re-start with P115 function selection = 2
"Motor identification at standstill".The ON
command must be given within 20 sec. after
the alarm message A078 = standstill
measurement has appeared.
Cancel the OFF command and re-start
measurement.

Table of Contents

Other manuals for Siemens simovert masterdrives

Related product manuals