EasyManua.ls Logo

Siemens simovert masterdrives

Siemens simovert masterdrives
1547 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
08.2012 Parameterizing Steps
Siemens AG 6SE7087-6QX70 (Version AN)
SIMOVERT MASTERDRIVES Compendium Motion Control 6-21
P352 = ?
Input the reference value for all frequency variables
(normalization variable for frequency limitations and frequency
setpoints and frequency actual values).
P353 = ?
Input the reference value for all speed variables
(normalization variable for speed limitations and speed setpoints
and speed actual values).
P354 = ?
Input the reference value for all torque variables
(normalization variable for torque limitations and torque
setpoints and torque actual values).
P452.1...4 = ?
Input the maximum speed in positive direction of rotation in %
(referred to P353).
If asynchronous motors are used (P095 = 2 or 4), only operation
up to twice the motor corner frequency (2 x P293) is permissible
in field weakening.
From version V2.30:
It is generally recommended when operating asynchronous
motors in field weakening to select a controller structure
optimized for this purpose (P296=3). This enables operation up
to 5 times the field weakening.
P453.1...4 = ?
P060 = 1
Return to the parameter menu
Input the maximum speed in negative direction of rotation in %
(referred to P353).
If asynchronous motors are used (P095 = 2 or 4), only operation
up to twice the motor corner frequency (2 x P293) is permissible
in field weakening.
From version V2.30:
It is generally recommended when operating asynchronous
motors in field weakening to select a controller structure
optimized for this purpose (P296=3). This enables operation up
to 5 times the field weakening.
When leaving the "Drive setting" menu, the entered parameter values
are checked for plausibility. Parameter settings that are not plausible
will lead to a fault. The wrongly set parameters are entered in
parameter r949 (fault value).
If current control is selected as the motor control, a suitable sensor
board (SBx) must be inserted beforehand and a permissible motor
encoder selected. If this is not carried out, the unit will also generate a
fault when it tries to leave the "Drive setting" menu.
NOTE

Table of Contents

Other manuals for Siemens simovert masterdrives

Related product manuals