EasyManua.ls Logo

Siemens simovert masterdrives

Siemens simovert masterdrives
1547 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions 09.2008
6SE7087-6QX70 (Version AK) Siemens AG
7-40 Compendium Motion Control SIMOVERT MASTERDRIVES
POS_OK forms the delay time from the time parameter 0 to 100.00 s
after reaching the target position in the window. A target position is
expected after a time of 0 to 100.00 s to be certain that the position is
held.
To influence POS OK externally or to ensure a handshake with another
unit or to hide the checkback, the signal is evaluated in parallel.
Setpoint mode output:
If the control binector "homing ON" [REF_ON] is active and travel takes
place in the selected direction REF_D, REF is set to HIGH to enable
the homing function on function diagram 789c.
Note: This signal is independent of status U866.1
ENABLE_POS/REF so that, when the positioner is enabled
again through status U866.1 ENABLE_POS/REF, status
ARFD = 1 is not reset.
(See the "Mode management" section.)
If the block is enabled (ENABLE_POS/REF = 1) and the "positioning
ON" binector [POS_ON] is active and if no homing movement
(REF_DRIVE = 1 ) is valid, status binector POS = 1 is shown.
(See the "Mode management" section.)
If the block is enabled (ENABLE_POS/REF = 1) and the "setup ON"
binector [SETUP_ON] is active and if no positioning or homing
movement (REF_DRIVE = 1 ) is active ([POS_ON] and [REF_ON] =
LOW), status binector [SETUP] = 1 is shown.
(See the "Mode management" section.)
If the "positioning" status binector [POS] or the "homing" status binector
[REF] or the "setup" status binector [SETUP] is active, this is shown
through the status binector [PSR] = HIGH.
If the block is enabled (ENABLE_POS/REF = 1 and
REF_TYP = 1 and REF_ON =1), REF_DRIVE is set to 1.
SET_REF_D (B0895) = REF_D (source U866.14), irrespective of all
operating modes.
The "current POS_TYP" status binector [POS_TYP_ACT] always
shows the signal level of the last valid, i.e. transferred, status binector
[POS_TYP].
See section about [POS_TYP] control binector.
[POS_TYP_ACT] = 0:
ABSOLUTE positioning through the [POS_TYP] control binector is
transferred/valid.
[POS_TYP_ACT] = 1:
RELATIVE positioning through the [POS_TYP] control binector is
transferred/valid.
POS_OK delay time
External position OK
B0871: REF homing
B0872: POS
positioning
B0873: SETUP
B0877: PSR
positioning/homing/
setup active
B0893: REF_DRIVE
homing movement
active
B0895: SET_REF_D
preferred direction
B0874:
POS_TYP_ACT
current POS_TYP

Table of Contents

Other manuals for Siemens simovert masterdrives

Related product manuals