09.2008 Communication / PROFIBUS
Siemens AG 6SE7087-6QX70 (Version AK)
SIMOVERT MASTERDRIVES Compendium Motion Control 8.2-9
Telegram:
Master Converter
PZD
(Setpoint channel)
PZD
1
STW1
PZD
2
HSW
PZD
3
PZD
4
PZD
5
PZD
6
PZD
7
PZD
8
PZD
9
PZD
10
1st
word
2nd
word
3rd
word
4th
word
5th
word
6
th
word
7th
word
8th
word
9th
word
10th
word
Combination values for:
16-bit process data 3001 3002 3003 3004 3005 3006 3007 3008 3009 3010
16-/32-bit process data (example) 3001 3032 3004 3035 3037 3039
Alternatives 3001 3032 3004 3005 3036 3038 3010
3001 3002 3003 3004 3035 3007 3038 3010
Process data quantity for:
PPO types 1 and 3 PZD2
PPO types 2 and 4 PZD6
PPO type 5 PZD10
Telegram:
Converter Master
PZD
(Actual-value channel)
PZD
1
ZSW1
PZD
2
HIW
PZD
3
PZD
4
PZD
5
PZD
6
PZD
7
PZD
8
PZD
9
PZD
10
Assignment of actual-value
parameters for
P734 P734 P734 P734 P734 P734 P734 P734 P734 P734
16-bit process data P694 P694 P694 P694 P694 P694 P694 P694 P694 P694
i001 i002 i003 i004 i005 i006 i007 i008 i009 i010
16-/32-bit process data (example) P734 P734 P734 P734 P734 P734 P734
P694 P694 P694 P694 P694 P694 P694
i001 i002 = i003 i004 i005 = i006 i007 i008 = i009 i010
Parameters for FC (CU1), VC (CU2) and SC (CU3)
PZD: Process data
STW: Control word
ZSW: Status word
HSW: Main setpoint
HIW: Main actual value
Table 8.2-2 Fixed assignment and combination values
If a second CBP is being operated in the converter, then the "8000"
connectors will be applicable for the second CBP instead of the "3000"
connectors, and parameter P736 will be applicable instead of para-meter
P734 (see function diagrams for CB/TB boards in Chapter 12).
NOTE