Configuration and Connection Examples 12.2010
6SE7087-6QX70 (Version AM) Siemens AG
2-38 Compendium Motion Control SIMOVERT MASTERDRIVES
Determination of MTTF
d
value
Parameter Value Comment
Channel 1
Safety relay –K1
B10
d
value 20.000.000 Specified by manufacturer
nop 24972 per year
24960 per year due to protective door
+ 12 per year due to Emergency Stop
MTTF
d
(-K1) 8008 years
op
d
d
n1,0
10B
MTTF
×
=
Interim result Channel 1
MTTF
d
(channel1)
8008 years
Capped to 100 years
Channel 2
Line contactor –K2
B10
d
value 1.333.333 Specified by manufacturer
nop 12 per year 12 per year due to Emergency Stop
MTTF
d
(-K2) 1,111,111 years
op
d
d
n1,0
10B
MTTF
×
=
Contactor relay –K3
B10
d
value 1.333.333 Specified by manufacturer
nop 24972 per year
24960 per year due to protective door
+ 12 per year due to Emergency Stop
MTTF
d
(contactor relay) 534 years
op
d
d
n1,0
10B
MTTF
×
=
Interim result Channel 2
MTTF
d
(channel2)
533 years
Capped to 100 years
=
)3K,2K(MTTF
1
)2channel(MTTF
1
dd
Interim results for REACT (channels 1 and 2)
MTTF
d
(REACT)
100 years
High
MTTF
d
values of both channels have been
capped to 100 years
It is not necessary to symmetrize both
channels.

Table of Contents

Other manuals for Siemens simovert masterdrives

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens simovert masterdrives and is the answer not in the manual?

Siemens simovert masterdrives Specifications

General IconGeneral
BrandSiemens
Modelsimovert masterdrives
CategoryDC Drives
LanguageEnglish

Related product manuals