EasyManua.ls Logo

Siemens SINAMICS S120 - Page 176

Siemens SINAMICS S120
438 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning
4.7 Basic parameterization of the drive objects
Commissioning with Startdrive
176 Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1
The function modules that can be used are presorted in two areas:
Frequently used function modules
Master/slave
Redundant operation of several ALMs on one DC link.
External Braking Module
Control of an external Braking Module in order to be able to collect braking energy in
the event of a power failure.
Additional function modules
Fault ride-through
For power generation applications in an interconnected system: Functions for fault
ride-through and line monitoring (incl. active anti-islanding) according to power system
guidelines.
Line droop control; installation, synchronization and operation of stand-alone systems:
Control of line frequency and line voltage in single operation or together with other
generators.
Line transformer
For power generation applications: Magnetization of a transformer to limit the inrush
current when the line system is connected.
Compensation for direct current components and voltage drops on the transformer in
conjunction with fault ride-through or line droop control.
Recorder
Recording fault events
Cosine Phi add-on module
Precise cos(Phi) determination based on fundamental current and voltage
components with BICO-connectable input variables (in contrast to power factor r0038).
Additional control
For applications with asymmetrical line voltages: A negative sequence system current
controller is used to balance the line currents and reduce the DC-link ripple.
For applications with resonance effects in the current or the filter voltage (e.g. in
systems with low short-circuit power rating): Freely parameterizable band-pass filters
for resonance damping
Activating function modules
1. Activate the required function module by clicking the option.
Repeat this for all additional function modules that you wish to activate.
2. Save the project to backup the settings.

Table of Contents

Other manuals for Siemens SINAMICS S120

Related product manuals