Commissioning
4.7 Basic parameterization of the drive objects
Commissioning with Startdrive
Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1
177
Line data / operating mode
You set the most important parameters for the operation of an infeed in the function view of
the "Line data / operating mode" screen form. The corresponding parameters are displayed
depending on the infeed type.
Figure 4-72 Example: Network data/operating mode for Active Line Module
The representation of this screen form is dependent upon the respective Line Module being
used:
Device supply
x x x -
DC-link voltage
setpoint default
x x - The value in this field (p3510) is deter-
mined automatically from the defined
Supply/DC-link
identification
x x - If the line supply / DC-link identification
has already been performed once, then
the value is preset to "OFF".
Operating mode for
ALM
x - - Presetting of the operating mode is de-
pendent upon the operating voltage of
the ALM:
≤ 415 V
eff
= Unregulated Udc (Active
Mode) active
≤ 415 V
eff
= Udc Regulated Udc (Active