Commissioning
4.7 Basic parameterization of the drive objects
Commissioning with Startdrive
Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1
179
You can connect several signal sources for the enables in the function view of the "Enable
logic" mask.
Figure 4-73 Enable logic
1. Interconnect the signal source via "p0840" for "OFF1 (low active)".
2. Interconnect the 1st signal source via "p0844" for "Instantaneous off (OFF2) signal
source 1".
3. Interconnect the 2nd signal source via "p0845" for "Instantaneous off (OFF2) signal
source 2".
4. Interconnect the signal source via "p0852" for "Enable operation".