Commissioning
4.7 Basic parameterization of the drive objects
Commissioning with Startdrive
194 Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1
4.7.4.5
Drive settings
No entries are required on this page for motors with DRIVE-CLiQ interface or motors of the
motor database.
Figure 4-83 Drive settings
Setting the automatic calculation of motor/control parameters
1. Select one of the following applications in the "Technology application" (p0500) drop-
down list:
Standard drive (VECTOR)
Pumps and fans
Encoderless control down to f = 0 (passive loads)
Dynamic response in the field weakening range
Approach with high break loose torque
High load inertia
2. In the drop-down list "Motor data identification and rotating measurement" (p1900), select
how the motor data identification is to be carried out for a stopped motor:
Inhibited
Motor data ident. (standstill) and speed controller opt.
With this setting, the drive is run up to speed upon 2nd actuation.
Identify motor data (standstill)
Optimize the speed controller (rotating)