Diagnostics
5.2 Diagnostics using LEDs
Commissioning with Startdrive
Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1
323
5.2.3.4
SMC40 Sensor Module Cabinet (only for direct measuring systems)
Table 5- 23 Meaning of the LEDs on the Sensor Module Cabinet-Mounted SMC40
LED
Color
Status
Description, cause
Remedy
RDY
READY
Off The electronics power supply is missing or outside the
permissible tolerance range.
Green Continuous
light
The component is ready for operation. Cyclic DRIVE-CLiQ
communication is taking place.
Orange Continuous
light
DRIVE-CLiQ communication is being established.
Red Continuous
light
This component has at least one fault.
Note:
LED is controlled irrespective of the corresponding mes-
sages being reconfigured.
Correct and
acknowledge the fault.
Green/red Flashing
light
2 Hz
Firmware download is complete. The system waits for
POWER ON.
Carry out a POWER
ON.
Green/
orange
or
Red/
orange
Flashing
light
Component recognition via LED is activated
1)
.
Note:
Both options depend on the LED status when component
recognition is activated.
1)
The parameters for activating component recognition can be taken from the following reference:
Reference: SINAMICS S120/S150 List Manual
Each channel has a multifunction LED.