Commissioning
4.7 Basic parameterization of the drive objects
Commissioning with Startdrive
204 Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1
4.7.5.2
Stationary/rotating measurement
Motor identification (MotID) provides a means of determining motor data, for example, of
third-party motors. To improve control properties of the motor, the MotID should be
performed. The main motor identification components are the stationary and rotating
measurements.
Adjustment
range
Explanation
Measurement
type
For selecting the measurement type (for experts)
Configuration
For entering configuration data for the selected measurement type (for experts)
Status
Indicates measurement progress
Measurement
result
Displays the measurement results of the MotID. The measurement results can be
corrected or accepted.
Figure 4-87 Stationary/rotating measurement
Note
If a power on or a warm restart is
performed when the motor data identification is selected,
then the motor data identification request is lost. A requested motor data identification must
be reselected manually after powering up.
Note
As long as a rotating measurement has been selected
and is running, you cannot perform
any upload, download, RAM to ROM or reset to the factory settings.
NOTICE
Damage to the device as a result of incorrectly selected rated current and/or maximum
current values
Incorrect rated current or maximum current data can destroy the motor!
Check that the current values that have been entered are correct.