Commissioning
4.10 Safety Integrated commissioning
Commissioning with Startdrive
246 Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1
Configuring SBR
1. Select the setting "with SAM" in the "Monitoring" drop-down list in the "SS1" or "SS2"
screen form.
The "SBR (Safe Brake Ramp)" dialog opens.
2. Enter the required values in the input fields.
Reference velocity (p9581)
SAM velocity limit (p9568)
STO shutdown speed (p9560)
Delay time (p9582)
Brake ramp monitoring time (p9583)
Ramp-down time (OFF3) (p1135[0])
Maximum speed (p1082[0])
3. Confirm your entry with "OK".
The dialog closes.
4.10.4.7
SBT (diagnostic function)
The diagnostic function "Safe Brake Test" ("SBT") checks the holding torque of a brake
(operating or holding brake). The drive purposely generates a configurable torque against
the applied brake. If the brake is operating correctly, the axis movement remains within a
parameterized tolerance. However, if a larger axis movement is identified from the encoder
actual values, the brake is not in a position to provide the specified holding torque. The brake
must now be serviced or replaced.
Precondition
The "Safe Brake Test" (SBT) diagnostic function can only be used with an encoder.
Features
The "SBT" diagnostic function has the following properties:
The parameters of the "SBT" function are protected by the safety password, and can only
be changed in the safety commissioning mode.
Using this function, brakes can be tested that are directly connected to the
SINAMICS S120 (integrated brake control), but also externally controlled brakes (e.g. via
a PLC).