Diagnostics
5.2 Diagnostics using LEDs
Commissioning with Startdrive
Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1
329
Red Continuous
light
This component has at least one fault.
The LED is activated irrespective of whether the correspond-
ing messages have been reconfigured.
Remove and
acknowledge the
fault.
Green/
red
Flashing
light
Firmware is being downloaded. -
Flashing
light
Firmware download is complete. The system waits for
POWER ON.
Carry out a POWER
ON.
Green/
orange
or
red/
Flashing
light
2 Hz
Component recognition via LED is activated
1)
.
Both options depend on the LED status when component
recognition is activated.
-
The parameter for activating component recognition using LEDs can be taken from the following reference:
Reference: SINAMICS S120/S150 List Manual
Table 5- 32 Meaning of the LEDs at the Terminal Module TM150
READY
– Off Electronic power supply is missing or outside permissible
Check power supply
Green Continuous
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
–
Orange Continuous
DRIVE-CLiQ communication is being established. –
Red
Continuous
light
This component has at least one fault.
LED is controlled irrespective of the corresponding mes-
sages being reconfigured.
Remedy and
acknowledge fault
Green/
Red
Flashing
light
Firmware is being downloaded. –
Flashing
light
Firmware has been downloaded.
Wait for POWER ON.
Carry out a POWER
ON
Green/
orange
or
red/
Flashing
light
2 Hz
Component recognition via LED is activated (p0154).
Both options depend on the LED status when module
recognition is activated via p0154 = 1.
–