EasyManua.ls Logo

Siemens SINAMICS S120 - Page 187

Siemens SINAMICS S120
438 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning
4.7 Basic parameterization of the drive objects
Commissioning with Startdrive
Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1
187
Entering the sampling times manually
If you have set "Expert" in p0112, you can manually configure each of the following sampling
times for the following control loops (p0115):
p0115[0]: Sampling times for internal control loops, current controller
p0115[1]: Sampling times for internal control loops, speed controller
p0115[2]: Sampling times for internal control loops, flux controller
p0115[3]: Sampling times for internal control loops, setpoint channel
p0115[4]: Sampling times for internal control loops, position controller
p0115[5]: Sampling times for internal control loops, positioning
p0115[6]: Sampling times for internal control loops, technology controller
Note
You cannot
set the values arbitrarily. The rules when setting the sampling times are listed in
Chapter "
Rules on the sampling times (Page 394)."
Enter the sampling times for the internal control loops.
Setting the pulse frequency
Set the pulse frequency via p1800.

Table of Contents

Other manuals for Siemens SINAMICS S120

Related product manuals