Commissioning
4.7 Basic parameterization of the drive objects
Commissioning with Startdrive
Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1
189
Connecting signal sources
1. Connect the signal source for the "Infeed operation" (p0864) command.
2. Connect the signal source for the "OFF1 (low active)" command (p0840).
This command corresponds to control word 1 bit 1 (STW1.1) in the PROFIdrive profile.
3. Connect the 1st signal source for the "OFF2 (low active) signal source 1" command
(p0844).
This command corresponds to control word 1 bit 1 (STW1.1) in the PROFIdrive profile.
4. Connect the 2nd signal source for the "OFF2 (low active) signal source 2" command
(p0845).
5. Connect the 1st signal source for the "OFF3 (low active) signal source 1" command
(p0848).
This command corresponds to control word 1 bit 2 (STW1.2) in the PROFIdrive profile.
6. Connect the 2nd signal source for the "OFF3 (low active) signal source 2" command
(p0849).
This command corresponds to control word 1 bit 2 (STW1.2) in the PROFIdrive profile.
7. Interconnect the signal source for the "Enable operation" command (p0852).
This command corresponds to control word 1 bit 3 (STW1.3) in the PROFIdrive profile.