Commissioning
4.7 Basic parameterization of the drive objects
Commissioning with Startdrive
Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1
201
3. Confirm your entries with "OK".
The "Measured signals" dialog closes.
You can then specify the optimization type.
4. Select the desired optimization type in the "Optimization objective" drop-down list.
– Robust (default setting)
– Moderate
– Tight
Performing optimization measurements
Note
Enabling the "Start" button
Certain operations can prevent the ena
bling of the "Start" button to start the optimization
measurements. The reasons for the prevented enabling are displayed in the messages in
the Inspector window.
Typical reasons for a prevented enabling are:
The drive is turning
The drive optimization is already active
The trace recorder is not available