Diagnostics
5.4 Fault and alarm messages
Commissioning with Startdrive
358 Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1
Properties of faults and alarms
Faults (code F01234)
Are identified by Fxxxxx.
Can lead to a fault reaction.
Must be acknowledged once the cause has been remedied.
Status via Control Unit and LED RDY.
Status via PROFIdrive status signal ZSW1.3 (fault active).
Entry in the fault buffer.
Alarms (code A56789)
Are identified by Axxxxx.
Have no further effect on the drive.
The alarms are automatically reset once the cause has been remedied. No
acknowledgement is required.
Status via PROFIdrive status signal ZSW1.7 (alarm active).
Entry in the alarm buffer.
General properties of faults and alarms
Can be configured (e.g. change fault to alarm, fault reaction).
Triggering on selected messages possible.
Initiation of messages possible via an external signal.
Contains the component number for identifying the SINAMICS component involved
Contains diagnostic information on the message involved