Diagnostics
5.4 Fault and alarm messages
Commissioning with Startdrive
Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1
367
These attributes for differentiating the alarms are assigned to the appropriate alarm
numbers. The reaction to the existing alarm classes in the alarm is defined by the user
program in the higher-level control.
Explanations of the alarm classes
Alarm class A: Drive operation currently not limited
E.g. alarm when measurement systems inactive
No limitation on current movement
Prevent possible switching to the defective measuring system
Alarm class B: Time-limited operation
E.g. prewarning temperature: Without further action the drive may need to be switched
off
After a timer stage -> additional fault
After exceeding a switch-off threshold -> additional fault
Alarm class C: Functionally limited operation
E.g. reduced voltage/current/torque/speed limits (i2t)
E.g. continue with reduced accuracy / resolution
E.g. continue without encoder