Appendix
A.5 System rules, sampling times and DRIVE-CLiQ wiring
Commissioning with Startdrive
Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1
395
Line Modules
For Active Line Modules (ALM) and Smart Line Modules (SLM) in booksize format, the
only current controller sampling time which can be set is 125 µs or 250 µs.
For Basic Line Modules (BLM), the only current controller sampling time that can be set is
250 µs (booksize format).
Motor Modules
For Single Motor Modules in booksize format, a current controller sampling time of
minimum 31.25 µs can be set (31.25 µs ≤ p0115[0] ≤ 500 µs).
For Double Motor Modules in booksize format, a current controller sampling time of
minimum 62.5 µs can be set (62.5 µs ≤ p0115[0] ≤ 500 µs).
Servo control
For servo control, a current controller sampling time between 31.25 µs and 250 µs can be
set (31.25 µs ≤ p0115[0] ≤ 250 µs).
The fastest sampling time of a drive object in the servo control mode is obtained as
follows:
T
i
= 31.25 µs: Exactly one drive object in servo control
T
i
= 62.5 µs: Max. 3 drive objects in servo control
T
i
= 125 µs: Max. 6 drive objects in servo control
Vector control / V/f control
A current controller sampling time between 125 µs and 500 µs can be set for vector
control (125 µs ≤ p0115[0] ≤ 500 µs). This also applies for operation with V/f control.
For vector control and vector control V/f control, and when using a sine-wave filter (p0230
> 0), it is only permissible to change the current controller sampling time of the DO
involved in multiple integer steps of the default value on account of the design of the sine-
wave filter.
The fastest sampling time of a drive object in vector control is obtained as follows:
T
i
= 250 µs: Max. three drive objects in vector control
T
i
= 375 µs: Max. four drive objects in vector control
T
i
= 400 µs: Max. five drive objects in vector control
T
i
= 500 µs: Max. six drive objects in vector control
The fastest sampling time of a drive object in V/f control mode is obtained as follows:
T
i
= 500 µs: Max. 12 drive objects in V/f control mode
When vector control is operated together with vector control V/f control, a maximum of 11
axes is possible (ALM, TB and TM also possible).
Safety functions
Only Single Motor Modules are permissible for servo control with a current controller
sampling time T
IReg
≤ 62.5 μs with the "Safety sensorless" functionality.