A.5 System rules, sampling times and DRIVE-CLiQ wiring
Commissioning with Startdrive
400 Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1
Drive topologies with DRIVE-CLiQ components that are not supported (by the type and
the firmware version of the Control Unit) are not permitted.
The sampling times (p0115[0] and p4099) of all components that are connected to a
DRIVE-CLiQ line must be divisible by one another with an integer result, or all the
sampling times set for the components must be an integer multiple of a common "base
cycle".
Example 1: A Line Module with 250 µs and a Motor Module with 125 µs can be
operated together on a DRIVE-CLiQ line ("base cycle": 125 µs)
Example 2: A Line Module with 250 µs and a Motor Module with 375 µs can be
operated together on a DRIVE-CLiQ line ("base cycle": 125 µs)
If the current controller sampling time T
i
at one drive object has to be changed in a
sampling time that does not match the other drive objects in the DRIVE-CLiQ line, the
following solutions are available:
Insert the modified drive object into a separate DRIVE-CLiQ line. Note here that a total
of 2 cycle levels are permissible on a Control Unit.
Modify the current controller sampling times and/or the sampling times of the
inputs/outputs of the other drive objects similarly so they match the modified sampling
time again.
Rules and instructions for avoiding overloads
In general any overload must be avoided of a DRIVE-CLiQ line and the components
connected to it through too many components with small sampling times. The following rules
and instruction apply for this:
A DRIVE-CLiQ line with components with a sampling time of T
i
= 31.25 μs
may only be
connected with components that are permitted for this sampling time. The following
components are permissible:
Single Motor Modules in booksize format
Sensor Modules SMC20, SMI20, SMI24, SME20, SME25, SME120 and SME125
High-frequency damping modules (HF damping modules)
Additional DRIVE-CLiQ lines must be used for additional components.
With current controller sampling times 31.25 µs and 62.5 µs the axes to the DRIVE-CLiQ
connections must be distributed as follows:
DRIVE-CLiQ socket X100: Infeed, axes 2, 4, 6, ...
DRIVE-CLiQ socket X101: Axes 1, 3, 5, ...
With a current controller sampling time of 31.25 μs, a filter module should be directly
connected to a DRIVE-CLiQ socket of the Control Unit.
A maximum of four Motor Modules with Safety Extended Functions may be operated on
one DRIVE-CLiQ line (for current controller sampling time T
IReg
= 125 μs on all axes). No
further DRIVE-CLiQ components other than a Line Module and Sensor Modules may be
connected to this DRIVE-CLiQ line.
Exception: For SINAMICS S120M, a maximum of 6 S120M with Safety Extended
Functions can be operated on one DRIVE-CLiQ line.