Line Connection Booksize   
2.9 Active Interface Modules internal air cooling 
  Booksize power units 
96  Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6 
Replacing the fan in an Active Interface Module 
 
NOTICE 
 
When replacing the fan, you must observe the ESD regulations. 
 
NOTICE 
 
Parts must only be replaced by trained personnel (danger of damage to sensitive 
components due to static electricity)! 
 
DANGER 
 
Before replacing the fan, you must switch off the power supplies (24 V DC and 400 V AC). 
Risk of electric shock. Dangerous voltages are still present for up to 5 minutes after the 
power supply has been switched off. The fan cover must not be opened until this time has 
elapsed.