Condition
CAUTION
Damage to property due to overload of digital outputs
If digital outputs are over
loaded, this can result in damage due to re, device defects, or
malfunctions.
• Ensure that the digital outputs are not loaded in excess of 100mA.
• Install a 100 mA fuse for connection to the digital output.
Connection example
You can connect DO0, DO1, and DO2 as shown below:
&RQYHUWHU
'LJLWDORXWSXW
/RDG
9
3
B'2
0(;7B'2
9
Figure6-11 NPN wiring
You can connect DO3, DO4, and DO5 as shown below:
&RQYHUWHU
/RDG
)XVH
'2
9
'2
P$
NPN wiring
&RQYHUWHU
/RDG
)XVH
'2
9
'2
P$
PNP wiring
More information
For more inf
ormation about the technical data of digital outputs, see Section "General technical
data (Page504)".
Connecting
6.8Connecting the inputs and outputs
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA 151