Condition
CAUTION
Damage to property due to overload of digital outputs
If digital outputs are over
loaded, this can result in damage due to 󹪝re, device defects, or
malfunctions.
Ensure that the digital outputs are not loaded in excess of 100mA.
Install a 100 mA fuse for connection to the digital output.
Connection example
You can connect DO0, DO1, and DO2 as shown below:
&RQYHUWHU
'LJLWDORXWSXW
/RDG
9
3
B'2
0(;7B'2


9
Figure6-11 NPN wiring
You can connect DO3, DO4, and DO5 as shown below:
&RQYHUWHU
/RDG
)XVH
'2
9
'2
P$
NPN wiring
&RQYHUWHU
/RDG
)XVH
'2
9
'2
P$
PNP wiring
More information
For more inf
ormation about the technical data of digital outputs, see Section "General technical
data (Page504)".
Connecting
6.8Connecting the inputs and outputs
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA 151