The maximum input pulse frequency for the high-speed 5V dierential pulse train input
(RS485) channel is 4 MHz. The c
hannel supports wire-break detection for input pulse
frequency up to 1MHz. When the converter detects a disconnection in the wire, it outputs
fault F07217.
For the high-frequency input signal (>200kHz), Siemens recommends that you set the lter
time for the pulse train input signals (p0438) to 0.04us.
9.5.3 Selecting a setpoint pulse train input form
Overview
The converter supports three kinds of setpoint pulse train input forms:
• AB phase pulse
• CW + CCW pulse
• Pulse + Direction
The available pulse train input form depends on the connected controller.
Functions
9.5Fast position control with pulse train input (Fast PTI)
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2