7.3 Getting started
7.3.1 Calling the web serv
er
Overview
Converter commissioning takes place with the user interface of the web server.
Requirement
• You have connected the converter and the operating unit via the service interface X127.
Procedure
To access the web server, enter the IP address of the converter, e.g. https://169.254.11.22, in the
browser.
More information
When you call the web server for the rst time, you are prompted to dene the basic settings.
If you have already made the basic settings, then the web server starts and opens the home
page. You can commission the converter, troubleshoot it, operate it, monitor it or call up
support through the support pages.
7.3.2 Settings for brand-new converters
Overview
The basic settings are required before performing rst commissioning for a brand-new
converter.
Requirement
• The operating unit is connected to the converter via the service interface X127.
• The web server is accessed with the IP address (default: 169.254.11.22).
Description of function
If the web server is called, a forwarding function starts automatically to dene the following
settings:
• Basic settings (Page174)
• Security settings (Page174)
Commissioning (web server)
7.3Getting started
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA 173