4.8.6 Shielded cables for the converter
Description
The following cables mus
t be shielded to comply with EMC regulations:
Inside the control cabinet:
Cable between the converter and line 󹪝lter
Signal and data cables
Outside the control cabinet:
Motor connection cables
Signal and data cables
To achieve EMC-compliant installation of the converter, connect the shields of the power
cable to the shield plate via the shield clamps. The shield plate is shipped with the converter.
For better EMC e󹪜ects, Siemens recommends that you strip the brake cable, encoder cable,
and setpoint cable, and connect the cable shields to earth. Make sure that the shield plate,
the converter and the motor are properly grounded.
5HPRYHWKHLQVXODWLRQDQG
H[SRVHWKHFDEOHVKLHOG
&RQQHFWVKLHOGVRIWKHEUDNH
FDEOHDQGHQFRGHUFDEOHWRWKH
VKLHOGSODWH
&RQQHFWVKLHOGRIWKHVHWSRLQWFDEOHWRWKH
PRXQWLQJSODWH0DNHVXUHWKHPRXQWLQJ
SODQHLVZHOOJURXQGHG
Figure4-2 Recommended EMC-compliant shield connection
Application planning
4.8EMC-compliant installation
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA 91