4.8.7 Achievable EMC category
Overview
The serv
o drive system has been tested in accordance with the emission requirements of IEC
61800‑3 CategoryC2.
For a radiated emission test, an external line 󹪝lter (between the mains supply network and
the converter) is required to meet the EMC requirements. The converter needs to be installed
inside a shielded metallic cabinet, while other parts of the motion control system (including
the PLC, DC power supply, spindle drive, and motor) need to be put outside the shielded
cabinet.
For a conductive emission test, an external line 󹪝lter (between the mains supply network and
the converter) is required to meet the EMC requirements.
For the radiated emission and conductive emission tests, the length of the line supply cable
between the line 󹪝lter and the converter must be shorter than 1m.
Description
The achievable EMC category is dependent on the motor cable length and the line system
con󹪝guration. The following conditions apply to the possible application environment.
Requirements Achievable EMC Category
C2 C3
Converter With line 󹪝lters C2 Wit
h line 󹪝lters C2 or C3
Maximum permis‐
sible cable length
Motor 30 m shielded 30 m shielded
Line 󹪝lt
er to the con‐
vert
er
3 m 3 m
Permissible appli‐
cation environ‐
ment
Residential No No
Light industrial
Yes Yes
Commercial Yes Yes
Permissible line
sy
stem
Public Yes Yes
Non-public Yes Yes
Line system con󹪝gur
ation TN or TT line syst
em with a
grounded neutral point
TN or TT line system with a
grounded neutral point
Note
T
o be obser
v
ed f
or de
vices used in Category C2
In a residential environment this product may cause radio-frequency interference, which may
make interference suppression measures necessary.
Have quali󹪝ed personnel carry out the installation and commissioning with suitable
interference suppression measures.
Application planning
4.8EMC-compliant installation
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
92 Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA