Description of function
One of the following options can be selected:
"Con󹪝gure security settings"
Siemens recommends this setting for comprehensive protection.
"Continue with low security settings"
With this setting, UMAC is deactivated.
You can con󹪝gure the security settings at a later time, see Section "Protection & Security
(Page213)".
Select "Con󹪝gure security settings"
De󹪝ne the settings for UMAC:
"Activate User Management & Access Control":
Activation is preset.
If UMAC is activated, it can only be deactivated by a full reset of the converter to factory
settings. This causes all security settings to be lost.
You can 󹪝nd more information about the full reset to factory settings in Section "Restore
factory settings (Page209)".
"Administrator setup":
Specify the user name and password of the drive administrator.
The drive administrator is permanently assigned the runtime role "Drive Administrator". This
assignment cannot be changed.
"Guest access con󹪝guration":
Specify whether the user has read rights without logging in and whether the user is allowed
to acknowledge results without logging in.
The option is deactivated in the factory setting. If guest access is not permitted, then the login
page is displayed when the web server is called.
De󹪝ne the settings to access the web server:
"Web server activation":
The factory setting to access the web server is service interface X127 with HTTPS protocol.
It is also possible to enable web server access via the service interface X127 with HTTP
protocol.
Assign an additional password for encryption of the drive data:
"Drive data encryption":
The function is activated by default.
The function encrypts sensitive data in the backup 󹪝le and on the memory card of the
converter. UMAC user data and passwords are sensitive data.
To use function "Drive data encryption" independent of UMAC, option "Activate UMAC for the
drive" must be deselected on page "Activate User Management & Access Control".
Check the con󹪝gured settings:
"Summary":
The summary provides an overview of the con󹪝gured settings.
Finish and continue
The settings are checked by clicking on "Finish". If there is no error, the settings are applied.
Commissioning (web server)
7.3Getting started
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA 175