Note
Analog torque limit for S200PTI
F
or S200PTI, when the signal TLM1-TLM0 status is 0-1, p29050[1] is invalid and the analog
voltage from the analog input 1 is used as the torque limit.
The analog voltage from the analog input 1 corresponds to an internal percentage value. Default
torque value is the rated motor torque (r0312). The analog voltage of 10 V corresponds to the
rated motor torque.
The following diagram shows how the internal torque limit functions. When the torque
setpoint reaches the t
orque limit, the actual torque output is limited to the value selected by
TLIM0/TLIM1.
W
7RUTX
H
/LPLWYDOXH
$FWXDOWRUTXHRXWSXW
7RUTXHVHWSRLQW
Overall torque limit
The overall tor
que limit takes eect when a quick stop (OFF3) happens. In this case, the servo
drive brakes with a maximum torque.
Table 9-23 Parameter - overall torque limit
Parameter Value range Default Unit Description
p1520 -1000000.00 ... 20000000.00 0 Nm Overall torque limit (upper)
p1521 -20000000.00 ... 1000000.00 0 Nm Overall torque limit (lower)
Torque limit reached (TLR)
When the generated t
orque has nearly (internal hysteresis) reached the value of the upper
torque limit, lower torque limit or analog torque limit, the signal TLR is output.
Parameters
The following list includes the parameters of the "Torque limit" function.
Number Name Unit
p0312[0] Rated motor torque [Nm]
p1520[0] Torque limit upper [Nm]
p1521[0] Torque limit lower [Nm]
Functions