EasyManua.ls Logo

Siemens SINAMICS S200 - Page 261

Siemens SINAMICS S200
764 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Note
Analog torque limit for S200PTI
F
or S200PTI, when the signal TLM1-TLM0 status is 0-1, p29050[1] is invalid and the analog
voltage from the analog input 1 is used as the torque limit.
The analog voltage from the analog input 1 corresponds to an internal percentage value. Default
torque value is the rated motor torque (r0312). The analog voltage of 10 V corresponds to the
rated motor torque.
The following diagram shows how the internal torque limit functions. When the torque
setpoint reaches the t
orque limit, the actual torque output is limited to the value selected by
TLIM0/TLIM1.
W
7RUTX
H
/LPLWYDOXH
$FWXDOWRUTXHRXWSXW
7RUTXHVHWSRLQW
Overall torque limit
The overall tor
que limit takes e󹪜ect when a quick stop (OFF3) happens. In this case, the servo
drive brakes with a maximum torque.
Table 9-23 Parameter - overall torque limit
Parameter Value range Default Unit Description
p1520 -1000000.00 ... 20000000.00 0 Nm Overall torque limit (upper)
p1521 -20000000.00 ... 1000000.00 0 Nm Overall torque limit (lower)
Torque limit reached (TLR)
When the generated t
orque has nearly (internal hysteresis) reached the value of the upper
torque limit, lower torque limit or analog torque limit, the signal TLR is output.
Parameters
The following list includes the parameters of the "Torque limit" function.
Number Name Unit
p0312[0] Rated motor torque [Nm]
p1520[0] Torque limit upper [Nm]
p1521[0] Torque limit lower [Nm]
Functions
9.5Fast position control with pulse train input (Fast PTI)
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA 259

Table of Contents

Other manuals for Siemens SINAMICS S200

Related product manuals