Remedy: - Check the heat sink fan and replace if necessary.
- For communication errors, updat
e the software or replace the power unit.
Note:
- If the fault can be acknowledged, this does not necessarily mean that the cause of the fault has been resolved. It is also
possible that the software switched o󹪜 the fan, and therefore can no longer evaluate the feedback signal.
F30059 Power unit: Internal fan 1 defective
Message class: Auxiliary unit faulted (20)
Message value: %1
Component: Power Unit
Response: OFF2
Acknowledgment: IMMEDIATELY
Cause: The feedback signal of internal fan 1 signals a fault, or there is a communication error with the fan.
F
ault v
alue (r0949, int
erpr
e
t decimal):
0: Feedback signal of the fan signals a fault
1: Internal communication error to the fan
Remedy: - Check internal fan 1 and replace if necessary.
- For communication errors, updat
e the software or replace the power unit.
Note:
If the fault can be acknowledged, this does not necessarily mean that the cause of the fault has been resolved. It is also
possible that the software switched o󹪜 the fan, and therefore can no longer evaluate the feedback signal.
F30062 Bypass contactor opened under current
Message class: Infeed faulted (13)
Message value: -
Component: Power Unit
Response: OFF2
Acknowledgment: IMMEDIATELY
Cause: The bypass contactor of the precharging unit has been opened under current.
P
ossible causes:
- A defect at the b
ypass contactor
Remedy: It is urgently recommended that the components involved are replaced to prevent serious damage to the entire converter
line-up.
F30068 Power unit: undertemperature inverter heat sink
Message class: Power electronics faulted (5)
Message value: %1
Component: Power Unit
Response: OFF2
Acknowledgment: IMMEDIATELY
Cause: The actual inverter heat sink temperature is below the permissible minimum value.
P
ossible causes:
- The power unit is being oper
ated at an ambient temperature that lies below the permissible range.
- The temperature sensor evaluation is defective.
Fault value (r0949, interpret decimal):
Inverter heat sink temperature [0.1 °C].
Remedy: - Ensure that higher ambient temperatures prevail.
- Replace the power unit.
System messages
11.3Faults and alarms
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
450 Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA