Remedy: - Check the device supply voltage (p0210).
- Check the dimensioning of the line react
or.
See also: p0210 (Device supply voltage)
C30603 SI: Module temperature - limit value exceeded
Message class: Safety monitoring channel has identied an error (10)
Message v
alue: -
Variant: S200 PTI
Component: None
Response: OFF2
Acknowledgment: IMMEDIATELY
Cause: A safe monitoring function has detected that the module temperature has exceeded a limit value. STO (Safe Torque O)
was
initiated to maint
ain the safe state.
Remedy: - Check the ambient temperature.
- Check the module fan.
- Operate t
he module in the permissible range.
F30604 SI: Safety EEPROM data error
Message class: Safety monitoring channel has identied an error (10)
Message v
alue: %1
Variant: S200 PTI
Component: Power Unit
Response: OFF2
Acknowledgment: POWER ON
Cause: Safety relevant EEPROM data are not correct.
This mes
sage results in an ST
O (Safe Torque O).
Message value (r60049, interpret decimal): Only for internal Siemens fault diagnostics.
Remedy: Replace the module
A30605 SI: Checksum error has occurred
Message class: Safety monitoring channel has identied an error (10)
Message v
alue: %1
Variant: S200 PTI
Component: None
Response: NONE
Acknowledgment: NONE
Cause: A checksum error (CRC error) has occurred in the converter program memory.
Remedy: - Carry out a POWER ON (switc
h-o/switch-on).
- Upgr
ade rmware to later version.
- Contact Technical Support.
C30649 SI: Internal software error
Message class: Hardware/software error (1)
Message value: Module: %1, line: %2
Variant: S200 PTI
Component: Power Unit
Response: OFF2
Acknowledgment: IMMEDIATELY
System messages
11.3Faults and alarms
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA 459