EasyManua.ls Logo

Siemens SINAMICS S200 - Page 467

Siemens SINAMICS S200
764 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Cause: Internal communications error.
Error cause:
1 (= 01 hex):
Check
sum error (CRC error).
2 (= 02 hex):
Telegram is shorter than speci󹪝ed in the length byte or in the receive list.
3 (= 03 hex):
Telegram is longer than speci󹪝ed in the length byte or in the receive list.
4 (= 04 hex):
The length of the receive telegram does not match the receive list.
5 (= 05 hex):
The type of the receive telegram does not match the receive list.
6 (= 06 hex):
The address of the power unit in the telegram and in the receive list do not match.
9 (= 09 hex):
The internal communications from the component involved signals a failure of the supply voltage.
16 (= 10 hex):
The receive telegram is too early.
17 (= 11 hex):
CRC error and the receive telegram is too early.
18 (= 12 hex):
The telegram is shorter than that speci󹪝ed in the length byte or in the receive list and the receive telegram is too early.
19 (= 13 hex):
The telegram is longer than that speci󹪝ed in the length byte or in the receive list and the receive telegram is too early.
20 (= 14 hex):
The length of the receive telegram does not match the receive list and the receive telegram is too early.
21 (= 15 hex):
The type of the receive telegram does not match the receive list and the receive telegram is too early.
22 (= 16 hex):
The address of the power unit in the telegram and in the receive list does not match and the receive telegram is too early.
25 (= 19 hex):
The error bit in the receive telegram is set and the receive telegram is too early.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy: - Carry out a POWER ON (switch-o󹪜/switch-on).
- Check the electr
ical cabinet design and cable routing for EMC compliance.
F30875 Power unit: power supply voltage failed
Message class: Supply voltage fault (undervoltage) (3)
Message value: Component number: %1, fault cause: %2
Component: Power Unit
Response: OFF2
Acknowledgment: IMMEDIATELY
Cause: The component involved has signaled that the 24 V supply has failed.
Er
r
or cause:
9 (= 09 he
x):
The po
w
er supply voltage for the components has failed.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
System messages
11.3Faults and alarms
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA 465

Table of Contents

Other manuals for Siemens SINAMICS S200

Related product manuals