Scenario 1: No drive passw
ord is con󹪝gured in the source and target converters.
1 2 3
$SFBUFCBDLVQ꫼MF
3FTUPSFESJWFEBUB
$POWFSUFS"
$POWFSUFS#$POWFSUFS#
୫3FQMBDFDPOWFSUFS"
ࡒ#
Click on "Restore".
The drive data are loaded int
o the converter from the backup 󹪝le.
As a consequence, the status of the settings at the instant of the backup are restored.
Scenario 2: No drive password is con󹪝gured in the source converter. On the other hand, in
the target converter function "Drive data encryption" had been previously activated and a
drive password con󹪝gured.
1 2 3
$SFBUFCBDLVQ꫼MF
3FTUPSFESJWFEBUB
%SJWFQBTTXPSEGPSDPOWFSUFS#
$POWFSUFS"
$POWFSUFS#$POWFSUFS#
୫3FQMBDFDPOWFSUFS"
ࡒ#


Click on "Restore".
A dialog to enter the passw
ord opens.
Enter the drive password of the target converter.
The drive data are loaded into the converter from the backup 󹪝le.
As a consequence, the status of the settings at the instant of the backup are restored.
Function "Drive data encryption" is activated. The con󹪝gured drive password is still
e󹪜ective in the target converter after data has been restored.
Corrective maintenance
12.1Service and maintenance for the converter
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA 489