On - Off
4 +1V ∘
∘
End-of-charge voltage
+ 26.3V fixed
5 +1V
6 +0.5V
7 +0.2V
8 +0.2V
9 +0.1V
10 0.35A / 0.7A Charging current
On - Off
1 Set time/max. time
2 +320 s ∘
∘
Buffer time
+5 s fixed
3 +160s
4 +80s
5 +40s
6 +20s
7 +10s
8 Disconnection
9 Battery operating state on/off
Legend:
Delivery condition setting
Setting for operation on the PCU
Configuration of the system
4.15 Configuring the SITOP UPS module for use with the PCU Base Software
PCU Base Software (IM10)
62 Commissioning Manual, 12/2017, 6FC5397-1DP40-6BA1