Table 86: Setpoints of the external PID controller
Index Parameter Min Max Unit Default ID Description
P3.14.2.1 Keypad Setpoint 1
P3.14.1.
8
P3.14.1.
9
Varies 0.00 1640
P3.14.2.2 Keypad Setpoint 2
P3.14.1.
8
P3.14.1.
9
Varies 0.00 1641
P3.14.2.3 Setpoint Ramp Time 0.00 300.00 s 0.00 1642
P3.14.2.4 Setpoint Selection
DigIN
Slot0.1
1048
OPEN = Setpoint 1
CLOSED = Setpoint 2
P3.14.2.5
Setpoint Source 1
Selection
0 32 1 1643
0 = Not Used
1 = Keypad Setpoint 1
2 = Keypad Setpoint 2
3 = AI1
4 = AI2
5 = AI3
6 = AI4
7 = AI5
8 = AI6
9 =ProcessDataIn1
10 =ProcessDataIn2
11 =ProcessDataIn3
12 =ProcessDataIn4
13 =ProcessDataIn5
14 =ProcessDataIn6
15 =ProcessDataIn7
16 =ProcessDataIn8
17 = Temperature Input
1
18 = Temperature Input
2
19 = Temperature Input
3
20 = Temperature Input
4
21 = Temperature Input
5
22 = Temperature Input
6
23 = Block Out.1
24 = Block Out.2
25 = Block Out.3
26 = Block Out.4
27 = Block Out.5
28 = Block Out.6
29 = Block Out.7
30 = Block Out.8
31 = Block Out.9
32 = Block Out.10
P3.14.2.6
Setpoint 1 Minimum -200.00 200.00 % 0.00 1644
P3.14.2.7 Setpoint 1 Maximum -200.00 200.00 % 100.00 1645
PARAMETERS MENU VACON · 175
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/