EasyManuals Logo

Vacon 100 flow Applications Manual

Vacon 100 flow
386 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #312 background imageLoading...
Page #312 background image
P3.13.6.5 RESPONSE TO PID SUPERVISION FAULT (ID 749)
Use this parameter to select the response of the drive to a 'PID Supervision' fault.
If the PID feedback value is not in the supervision limits for longer than the supervision delay,
a PID supervision fault occurs.
10.14.7 PRESSURE LOSS COMPENSATION
When you pressurise a long pipe that has many outlets, the best position for the sensor is in
the middle of the pipe (the position 2 in the figure). You can also put the sensor directly after
the pump. This gives the right pressure directly after the pump, but farther in the pipe, the
pressure drops with the flow.
PT PT
A
B
C
D
E F
Fig. 85: The position of the pressure sensor
A. Pressure
B. No flow
C. With flow
D. Pipe length
E. Position 1
F. Position 2
P3.13.7.1 ENABLE SETPOINT 1 (ID 1189)
Use this parameter to enable the pressure loss compensation in the pump system.
In a pressure controlled system, this function compensates the pressure loss that occurs at
the end of the pipe line due to the liquid flow.
P3.13.7.2 SETPOINT 1 MAX COMPENSATION (ID 1190)
Use this parameter to set the maximum compensation for PID setpoint value that is applied
when the output frequency of the drive is at the maximum frequency.
The compensation value is added to the actual setpoint value as a function of the output
frequency.
Setpoint compensation = max compensation * (FreqOut-MinFreq)/(MaxFreq-MinFreq).
VACON · 312 PARAMETER DESCRIPTIONS
10
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/

Table of Contents

Other manuals for Vacon 100 flow

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon 100 flow and is the answer not in the manual?

Vacon 100 flow Specifications

General IconGeneral
Protection classIP20
Communication interfaceRS-485
Operating temperature-10°C to +50°C
Storage temperature-40°C to +70°C
Ambient temperature-10°C to +40°C
Control methodSensorless vector control
Communication protocolsCANopen
ApprovalsCE, UL
I/O2 analog inputs
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature
Frequency range0 Hz to 400 Hz
Humidity5% to 95%, non-condensing
Voltage range208-240 V

Related product manuals