Table 95: Fire mode parameters
Index Parameter Min Max Unit Default ID Description
P3.17.9
Fire Mode Run Indi-
cation Current
0 100 % 10 15580
5.18 GROUP 3.18: MOTOR PREHEAT PARAMETERS
Table 96: Motor preheat parameters
Index Parameter Min Max Unit Default ID Description
P3.18.1
Motor Preheat Func-
tion
0 3 0 1225
0 = Not used
1 = Always in stop state
2 = Controlled by DI
3 = Temperature limit,
heatsink
P3.18.2
Preheat Tempera-
ture Limit
-20 100 °C/F 0 1226
P3.18.3
Motor Preheat Cur-
rent
0 0.5*I
L
A Varies 1227
P3.18.4 Motor Preheat ON Varies Varies
DigIN
Slot0.1
1044
OPEN = No action
CLOSED = Preheat
activated in Stop state
5.19 GROUP 3.19: DRIVE CUSTOMIZER
Table 97: Drive customizer parameters
Index Parameter Min Max Unit Default ID Description
P3.19.1 Operation Mode 0 1 1 15001
0 = Execute Program
1 = Programming
NOTE!
When you use the Drive customizer, use the graphical Drive customizer tool in
VACON
®
Live.
VACON · 182 PARAMETERS MENU
5
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/

Table of Contents

Other manuals for Vacon 100 flow

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon 100 flow and is the answer not in the manual?

Vacon 100 flow Specifications

General IconGeneral
Protection classIP20
Communication interfaceRS-485
Operating temperature-10°C to +50°C
Storage temperature-40°C to +70°C
Ambient temperature-10°C to +40°C
Control methodSensorless vector control
Communication protocolsCANopen
ApprovalsCE, UL
I/O2 analog inputs
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature
Frequency range0 Hz to 400 Hz
Humidity5% to 95%, non-condensing
Voltage range208-240 V

Related product manuals