29
Set a value for P3.15.7 Autochanged pumps
0 = Auxiliary pumps
1 = All pumps
Step 30 shows only if you set the value Enabled (Interval) to parameter Autochange in step 28.
30 Set a value for P3.15.8 Autochange Interval Range: 0-3000 h
Steps 31 and 32 show only if you set the value Enabled (Weekdays) to parameter Autochange
in step 28.
31
Set a value for P3.15.9 Autochange Days Range: Monday to Sunday
32 Set a value for P3.15.10 Autochange Time of Day Range: 00:00:00 to 23:59:59
33
Set a value for P3.15.11 Autochange Frequency
Limit
Range: P3.3.1.1-P3.3.1.2 Hz
34 Set a value for P3.15.12 Autochange Pump Limit Range: 1-8
35 Set a value for P3.15.13 Bandwidth Range: 0-100%
36
Set a value for P3.15.14 Bandwidth Delay
Range: 0-3600 s
The Multi-pump (single drive) application wizard is completed.
2.5 MULTI-PUMP (MULTIDRIVE) APPLICATION WIZARD
The application wizard helps you to set the basic parameters that are related to the
application.
To start the Multi-pump (multidrive) application wizard, set the value Multi-pump (Multidrive)
to parameter P1.2 Application (ID 212) in the keypad.
NOTE!
If you start the application wizard from the Startup wizard, the wizard goes directly
to step 11.
VACON · 84 WIZARDS
2
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/

Table of Contents

Other manuals for Vacon 100 flow

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon 100 flow and is the answer not in the manual?

Vacon 100 flow Specifications

General IconGeneral
Protection classIP20
Communication interfaceRS-485
Operating temperature-10°C to +50°C
Storage temperature-40°C to +70°C
Ambient temperature-10°C to +40°C
Control methodSensorless vector control
Communication protocolsCANopen
ApprovalsCE, UL
I/O2 analog inputs
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature
Frequency range0 Hz to 400 Hz
Humidity5% to 95%, non-condensing
Voltage range208-240 V

Related product manuals