P3.13.5.9 SP2 WAKE UP LEVEL (ID 1077)
Use this parameter to set the level at which the drive wakes up from the sleep state.
P3.13.5.10 SP2 WAKE UP MODE (ID 1020)
Use this parameter to select the operation for the wake up level parameter.
P3.13.5.11 SP2 SLEEP BOOST (ID 1794)
Use this parameter to set the value that is added to the actual setpoint value when the sleep
boost function is used.
P3.13.5.12 SP2 SLEEP BOOST MAXIMUM TIME (ID 1796)
Use this parameter to set the timeout time for the sleep boost function.
10.14.6 FEEDBACK SUPERVISION
Use the feedback supervision to make sure that the PID Feedback value (the process value
or the actual value) stays in the set limits. With this function you can, for example, find a pipe
break and stop the flooding.
These parameters set the range in which the PID Feedback signal stays in correct
conditions. If the PID Feedback signal does not stay in the range, and this continues longer
than the delay, a Feedback supervision fault (the fault code 101) shows.
P3.13.6.1 ENABLE FEEDBACK SUPERVISION (ID 735)
Use this parameter to enable the feedback supervision function.
Use the feedback supervision to make sure that the PID feedback value stays in the set
limits.
VACON · 310 PARAMETER DESCRIPTIONS
10
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/

Table of Contents

Other manuals for Vacon 100 flow

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon 100 flow and is the answer not in the manual?

Vacon 100 flow Specifications

General IconGeneral
Protection classIP20
Communication interfaceRS-485
Operating temperature-10°C to +50°C
Storage temperature-40°C to +70°C
Ambient temperature-10°C to +40°C
Control methodSensorless vector control
Communication protocolsCANopen
ApprovalsCE, UL
I/O2 analog inputs
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature
Frequency range0 Hz to 400 Hz
Humidity5% to 95%, non-condensing
Voltage range208-240 V